High Voltage Test and Measuring equipment (AC Test Set)100kV,10kVA

 

Consisting of:

SL NO
DESCRIPTION
TYPE
QTY
1 HV Test Transformer Pri. 220 V, 50Hz, Sec. 100kV, 5kVA continuous 10kVA 1Hr.on,23Hrs. off Partial Discharge < 3 pC upto rated voltage (100 kV) TEO100/10 1
2 Control Desk (Motorised) CD 10 1
3 Capacitor(Coupling / Measuring) 100kV,
100 pF PD < 3 pC
CM100 1
4 Voltmeter AC peak--- 4.5 Digit, Digital Display) DSM 1
5 Flexible connecter HSV 1

Pre-despatch Tests at our Works on No-Load :

Sl.No HV Transformer (Type TEO 100/10) Capacitor (Coupling / Measuring) Type CK 120
a No-Load and short circuit Tests HV withstand Test at 120 kV, 50Hz, for 1 minute
b HV withstand Test at 120 kV, 50 Hz, for 1 minute Measurement of Capacitance and Tan at 20% Voltage intervals
c Partial Discharge Test before and after the Test (b) and (c) at 20% Voltage Intervals. Measurment of Partial Discharge at 20% Voltage Intervals