High Voltage Construction Kit

 


Compensating Reactor

DEG 0.5/5 Resin Cast Compensating Reactor Technical data

Rated Voltage 220 V
Frequency 50 Hz.
Rated Output 1. 5 kVA (continuous) / 10 kVA 60 min.
2. 10 kVA (continuous) / 20 kVA 60 min.
Frequency 50 Hz. / 60 Hz.
Inductance 30mH - 15 mH
Dimension 425 x 462 x 190mm
Weight 100 kg

 

 

 

 

Test Out put of the Transformer in Cascade Connection

Without compensation for transformer TEO 100/10 With compensating reactor for transformer TEO 100/10 Without Compensation for transformer TEO 100/20 With compensating reactor for transformer TEO 100/10
Cascade Cont. Short Time Cont. Short Time No. of reactors Cont. Short Time
(approx)
Cont. Short Time
(approx)
No. of reactors
Single Stae 5 kVA 10kVA - - - 7.5kVA 20kVA - - -
Two Stage 5 kVA 10kVA 10kVA 20kVA 1 7.5kVA 20kVA 12.5kVA 30kVA 1
Three Stage 5 kVA 10kVA 15kVA 30kVA 2 7.5kVA 20kVA 17.5kVA 40kVA 2